Ermenrich Ping MK10 Digital Clamp Meter
Product ID | |
Brand | Ermenrich |
Warranty | 5 years |
EAN | 5905555017440 |
Package size (LxWxH) | 18x10x4 cm |
Shipping Weight | 0.245 kg |

Find out more
The device combines the functions of a voltmeter (measurement of direct and alternating voltage), ammeter (measurement of alternating current), and ohmmeter (measurement of resistance). Calculations are carried out using True RMS, and so the measurement accuracy of variable quantities is high. The additional functionality of the model includes checking circuit continuity and testing diodes for faults.
The measurement results and operating parameters of the device are displayed on the built-in screen. The screen backlight makes it easy to work in low light and complete darkness. There is a Data Hold function, which is useful in a situation where it is impossible to immediately take readings from the device. When activated, they will be “frozen” on the screen and can be accessed later.
The device requires a pair of standard batteries to operate. The auto-off function helps save power. When the batteries are low, a notification will appear thereby indicating that they need to be replaced.
Key features:
- Measurement of AC current without breaking the circuit
- Determination of direct and alternating voltage, resistance
- Diagnostics of diodes for malfunctions (open and short circuits), circuit testing for short circuits and open circuits
- Data Hold function to freeze readings on the screen, saves the maximum value
- True RMS – calculation of variables with a high accuracy
- Battery-powered, auto-off function
The kit includes:
- Clamp meter
- Probes
- User manual and warranty card
Product ID | |
Brand | Ermenrich |
Warranty | 5 years |
EAN | 5905555017440 |
Package size (LxWxH) | 18x10x4 cm |
Shipping Weight | 0.245 kg |
Selection of the measuring limit | automatic, manual |
Basic functions | ammeter, ohmmeter, voltmeter |
DC voltage measuring limit | 200mV/2V/20V/200V/600V: error ±(0.5%+5) |
AC voltage measuring limit | 2/20/200/600V: error ±(1.0%+5) |
AC current measuring limit | 2/20/200А: error ±(2.5%+8) |
Resistance measuring limit | 200Ω/2kΩ/20kΩ/200kΩ/2MΩ/20MΩ: error ±(1.0%+5) |
Diodes test | ✓ |
True RMS | ✓ |
Hold function | ✓ |
Limit value function (Min/Max) | + (maximums only) |
Conductor continuity check | ✓ |
Overvoltage category | CAT III 600V |
Display counts | 2000 |
Display backlight | ✓ |
Safety standards | EN61010-1,-2-030; EN61010-2-033; EN61326-1 |
Power supply | 2 AAA batteries (not included) |
Low battery status indicator | ✓ |
Auto power off | ✓ |